Case study · Hotel / Hospitality

Failing benchmark to first-pass AHJ approval

AC Hotel Ann Arbor, a 7-floor hotel in Ann Arbor, Michigan, failed its public-safety benchmark grid test — legally triggering an ERCES. WZC took it to full code coverage, approved on the first inspection.

Explore Public Safety DAS

  • First-pass AHJ approval
  • 7-floor hotel · 81,706 sq ft
  • Zero punchlist items

Engineered to pass the first inspection

Benchmark: failed grid test — Acceptance: first-pass approval

When AC Hotel Ann Arbor failed its public-safety benchmark grid test, the failure legally triggered an ERCES requirement. WZC ran the full process from there: predictive iBwave design and direct fire-marshal coordination, so the system on paper was the system the AHJ expected to see.

The installed system is a COMBA CriticalPoint Class A BDA feeding 54 ceiling dome antennas across 81,706 sq ft, backed by a 33.9-hour LiFePO4 battery system.

The acceptance grid test proved 95% general and 99% critical-area coverage with margin — earning first-pass AHJ approval with zero punchlist items.

All case studies

COMBA CriticalPoint Class A BDA — antenna installation

54

Ceiling dome antennas

81,706

Sq ft covered

95%

General coverage

99%

Critical-area coverage

33.9 hr

Battery backup

0

Punchlist items

  • Predictive iBwave design with fire-marshal coordination
  • COMBA CriticalPoint Class A BDA, 54 ceiling dome antennas
  • 33.9-hour LiFePO4 battery backup system
  • Acceptance grid test passed with margin — zero punchlist

From failed benchmark to margin above code

Acceptance grid-test results at AC Hotel Ann Arbor — 95% general and 99% critical-area coverage across 81,706 sq ft, approved on the first inspection.

  • IFC 510 general minimum: 95%
  • IFC 510 critical minimum: 99%
  • Benchmark grid test: FAIL — below code, ERCES triggered
  • Acceptance — general areas: 95%
  • Acceptance — critical areas: 99%
  • First-pass AHJ approval · 0 punchlist items · 54 dome antennas · 33.9-hr battery backup